Parallel redundant UPS VFI-SS-111system consisting of:
2 x tower and rack UPS systems with 6 kVA / 5.4 kW each
2 x rack-mount kit, 3 U each
1 x parallel kit incl. rack-mount kit, 3 U
UPS specifications:
USB and serial interfaces
Network card included
Mini terminal block for remote on/off and emergency-off switch
Input: Hardwired (single-phase)
Output: hardwired, 1-phase, 4 x IEC320-C19
Runtime at 5400 W: approx. 3 min
Runtime at 3700 W: approx. 8 min
Runtime at 2700 W: approx. 11 min
Net weight (per UPS): 48 kg (incl. standard battery pack)
Total weight: 106 kg
UPS must be connected by a professional electrician. Required fuses and wire gauge:
1-phase input: 32 A, min 6 mm²
parallel redundant UPS system with online stepdown technology consists of:
2 x tower and rack UPS systems with 11 kVA / 10 kW each
2 x rack-mount kit, 6 U each
1 x parallel kit incl. rack-mount kit, 3 U
UPS specifications:
USB and serial interfaces
Network card included
Mini terminal block for remote on/off and emergency-off switch
Input: Hardwired (single-phase)
Output: hardwired, 1-phase, 4 x IEC320-C19
Runtime at 10 kW: approx. 4 min
Runtime at 7000 W: approx. 7 min
Runtime at 5000 W: approx. 12 min
Net weight (per UPS): 86 kg (incl. standard battery pack)
Total weight: 187 kg
UPS must be connected by a professional electrician. Required fuses and wire gauge:
1-phase input: 63 A, 16 mm²